Key takeaways
- India's HFC consumption freezes in 2028, with step-downs from 2032 to an 85% cut by 2047.
- Existing equipment is not banned. The change works through supply and through the refrigerants new equipment uses.
- Leak-tight systems and proper recovery matter more as refrigerant supply tightens.
- Record the refrigerant in every unit now, so your 2027 buying decisions are informed.
A facility manager is asked to approve the purchase of twelve new split units for an office floor. The quotation lists the refrigerant as R-32. A colleague says he has read that “HFCs are being banned” and wonders whether the plant room’s R-410A package units and the old R-134a chiller will soon be illegal to run.
They won’t be. But the question is a fair one, because India has committed to a long-term cut in hydrofluorocarbons (HFCs), the family of refrigerants used in most air conditioning installed over the last two decades. The first step, a freeze, arrives in 2028. This article explains what has actually been decided, what has not, and what is sensible to do in 2027.
This is general guidance. Check the current notification and your own compliance requirements; regulations change.
What India has agreed to
The Kigali Amendment to the Montreal Protocol extends the ozone treaty to HFCs. HFCs do not damage the ozone layer, but many of them are powerful greenhouse gases.
- In August 2021 the Union Cabinet approved India’s ratification of the amendment, according to the Press Information Bureau.
- India ratified it on 27 September 2021 (PIB).
- India’s schedule is a freeze in 2028, followed by cuts of 10% in 2032, 20% in 2037, 30% in 2042 and 85% in 2047, measured against a baseline set from recent years. The agreement allows the freeze to be deferred to 2030 under certain conditions (PIB).
- A national strategy for the HFC phase-down was finalised in 2023, according to a 2025 government document.
The 2021 Cabinet decision also said that the national rules on ozone-depleting substances would be amended to cover HFCs. At the time of writing we have not been able to confirm that such an amendment has been notified, so check the Ministry of Environment’s Ozone Cell for the current position before you rely on any specific rule.
What changes in 2028, and what doesn’t
A phase-down limits how much HFC the country consumes. It is a cap on supply, not a ban on equipment.
What doesn’t change:
- Your existing ACs, package units and chillers that use HFCs such as R-410A, R-134a or R-32 can keep running.
- They can be serviced and repaired.
- No date has been set, as far as we can find, after which you must replace an HFC unit simply because of its refrigerant.
What is likely to change over time:
- As the allowed quantity is held and then reduced, availability and cost of some refrigerants may change, particularly for refrigerants with a high warming impact.
- Manufacturers will keep moving new equipment towards lower-impact refrigerants, some of which are flammable and need different handling.
- Good practice, such as leak checks and recovering refrigerant instead of venting it, becomes more valuable, because every kilogram lost has to be replaced from a shrinking supply.
Don’t confuse this with the earlier phase-out of HCFCs such as R-22. That one is further along: no new equipment has been made with HCFCs in India since 1 January 2025, while existing HCFC systems can be serviced until 2040, according to the Ozone Cell.
Which refrigerants are in your units today
Most sites run a mix. The nameplate on each outdoor unit, package unit or chiller states the refrigerant and the factory charge. Common ones you will find:
| Refrigerant | Family | Where you see it |
|---|---|---|
| R-22 | HCFC | Older split and package units, older chillers |
| R-410A | HFC | Many split, ducted and VRF systems |
| R-32 | HFC | Most new split ACs |
| R-134a | HFC | Many chillers and some precision cooling |
| R-290 (propane) | Hydrocarbon, not an HFC | Some newer small units |
R-32 is classed as mildly flammable (class 2L) and R-290 as flammable (class 3), according to the Ozone Cell’s handbook for technicians. Both need technicians trained in flammable refrigerants.
Five steps to take in 2027
1. Build a refrigerant register
List every unit with its location, model, refrigerant type, charge quantity from the nameplate, year of installation and condition. It takes a day or two for a typical site and answers most questions that come later. If you have a maintenance contract, ask your contractor to keep it up to date.
2. Check for leaks and fix them
A unit that needs topping up every summer is leaking. Ask for a proper leak check, fix the leak, then recharge to the nameplate quantity. Topping up a leaking system wastes refrigerant and money and hides a fault that will return.
3. Recover, don’t vent
When a unit is repaired, relocated or scrapped, the refrigerant should be recovered into a cylinder with a recovery machine, not released. Put this requirement in writing in your service contracts and ask for it to be recorded on the visit report.
4. Use trained technicians
Ask whoever services your equipment whether their technicians are trained for the refrigerants you run, especially flammable ones. The government has been supporting technician training: a 2018 agreement aimed to train 100,000 air conditioning service technicians (PIB).
5. Plan replacements, don’t wait for failures
Old units, especially R-22 ones, are the obvious candidates. Replacing them in a planned way, in the cooler months, is cheaper and calmer than replacing them in May when they fail.
Buying new equipment with the phase-down in mind
If you are buying in 2027, ask a few extra questions alongside capacity and efficiency:
- Which refrigerant does it use, and is it one that local technicians can service?
- Is it flammable? If so, does the installation location meet the manufacturer’s requirements on room size and ventilation?
- How much refrigerant does it hold? Smaller charges mean less to lose in a leak.
- What efficiency does it achieve? An efficient unit cuts running costs, whatever the refrigerant.
You don’t need to rush to replace working HFC equipment. You do need to know what you have, keep it tight, and buy new equipment with the next twenty years in mind.
We install, repair and maintain air conditioning, package units and precision cooling, and can build a refrigerant register as part of a maintenance contract. See our cooling and heating services, or request a quote for a survey of your site.
General guidance based on common engineering practice. Always follow the equipment manufacturer’s instructions and your site’s safety procedures.