Key takeaways
- Note the fault, when it happens (start, run, stop) and the load before changing anything.
- Overvoltage on deceleration usually means regenerated energy: check ramp times and the braking resistor.
- Earth and overcurrent faults often come from the motor or cable: test them before blaming the drive.
- If faults return on a new drive, the cause is elsewhere.
A conveyor drive trips on overcurrent every few hours. The team resets it, it runs, it trips again. After a week someone orders a new drive, fits it, and two days later the new drive trips with the same fault. The real cause, a motor cable chafed through where it enters a junction box, was there all along.
Variable frequency drives (VFDs) are good at protecting themselves. When a drive trips, it is usually reporting a problem outside itself: in the motor, the cable, the load, the supply or the settings. The fault code is the first clue, not the verdict. This guide goes through the common faults in general terms. Every manufacturer uses its own codes and names, so check your drive’s manual for the exact meaning and any fault history it stores.
Before you touch anything: record the fault
The minutes after a trip give you the clearest evidence. Before you reset or change settings, note:
- the exact fault code and text, and any secondary codes
- when it happened: during acceleration, at steady speed, during deceleration, or at stop
- the load at the time: empty, normal, heavy, or a sudden jam
- what the drive’s fault log shows: many drives store the output current, DC bus voltage, frequency and heatsink temperature at the moment of the trip
- anything that changed recently: a new motor, a cable rerouted, a parameter edited, a new machine on the same supply
- the pattern: every start, random, only on hot afternoons, only when another machine runs
Write it down or take photos of the display. This record will also save time if the drive does end up with a repairer; our guide on sending a unit for repair explains what else helps.
Overcurrent: at start, at speed, on stopping
An overcurrent trip means the drive saw output current above its protection limit, often for only microseconds. When it happens tells you most.
At start or during acceleration:
- Acceleration ramp too short for the inertia of the load.
- Mechanical binding: a seized bearing, a jammed conveyor, a brake that hasn’t released.
- Starting into a spinning motor (a fan turning in a draught) without the drive’s flying-start function enabled.
- Motor data entered wrongly, or an auto-tune not run after a motor change.
- Boost or torque settings too high.
At steady speed:
- A sudden mechanical load, such as a jam or a product pile-up.
- A short circuit or partial short in the motor or cable, which may appear only when the cable moves or warms up.
- A contactor between the drive and motor opening or closing while the drive is running. Most manufacturers forbid this unless the drive is designed for it.
On stopping: usually linked to the deceleration and braking settings, which leads to overvoltage below.
Checks in order: look at the load and the mechanics, check ramps and motor data, then isolate and test the motor and cable (see earth faults below). If the drive trips on overcurrent instantly with the motor cable disconnected, the fault is likely inside the drive.
Overvoltage on the DC bus
The drive rectifies the mains into a DC bus. If the bus voltage rises too high, the drive trips to protect its capacitors and transistors.
On deceleration, by far the most common case: when the drive slows a motor driving a high-inertia load, the motor acts as a generator and pushes energy back into the DC bus. If the drive can’t get rid of it fast enough, the bus voltage climbs.
- Lengthen the deceleration ramp, if the process allows.
- Check that the braking resistor, if fitted, is connected, the right value, not open-circuit and not overheated. Check the braking function is enabled in the parameters.
- Consider the drive’s own overvoltage control function, which slows the ramp automatically.
- For loads that regularly overhaul the motor, such as hoists and downhill conveyors, the braking arrangement needs to be sized for it.
At steady speed or at stop: suspect the supply. High mains voltage, voltage spikes from capacitor bank switching, or a generator with poor voltage regulation can all lift the DC bus. Measure the supply over time, ideally with a recorder.
Earth faults and insulation
An earth fault (or ground fault) trip means the drive detected current leaking to earth from its output. It almost always points to the motor or cable.
- Damaged cable insulation: chafing, rodent damage, crushing in cable trays, or water in junction boxes.
- Wet or contaminated motor windings, common after the monsoon or wash-downs.
- Long motor cables, which have higher capacitance to earth. Some drives need settings or output filters for long runs; check the manual’s limits.
Checks in order: isolate, disconnect the motor cable at the drive, then have a competent person test the insulation resistance of the motor and cable to earth with an insulation tester, at the test voltage the motor manufacturer recommends. Test the cable and motor separately if the first result is low. Inspect junction boxes for water and burnt marks.
If the motor and cable test healthy and the drive still reports an earth fault with the motor disconnected, the drive’s output stage or current sensing may be faulty.
Overheating and fan faults
Heatsink overtemperature and fan faults are rarely mysterious:
- cooling fans worn out or stopped
- heatsink fins clogged with dust or fibre
- panel filter mats blocked, or the panel’s own cooling not working
- the drive running above its rating, or above its derated rating at high ambient temperature or altitude
- a switching frequency set higher than needed, which increases losses
Clean, check the fans, measure the panel temperature on a hot afternoon, and compare the load current with the drive’s derating table.
When the fault is inside the drive
It is time to suspect the drive itself when:
- the fault appears with the motor disconnected (where the manual allows the drive to run without a motor for test purposes)
- the drive shows hardware, internal or power-stage faults, or won’t power up
- there are visible signs: burn marks, a smell of burnt components, bulging or leaking capacitors
- the same fault keeps returning after the motor, cable, load, supply and settings have all been checked
At that point, record the parameters if the drive will still communicate, and remove it. Drive faults such as failed power devices, capacitors, fans and power supply sections can often be repaired at component level, subject to inspection and parts availability. See our industrial component repair service.
And remember the conveyor at the start of this article. If a new or repaired drive shows the same fault soon after fitting, stop. The cause is outside the drive, and another drive will not fix it.
If you have a drive that keeps tripping, or one that has failed, send us the repair details with the fault codes and what happened before the trip.